Figure 343: Integral deadband supervision
The deadband value used in the integral calculation is configured with the X
deadband setting. The value represents the percentage of the difference between
the maximum and minimum limit in the units of 0.001 percent x seconds.
The reporting delay of the integral algorithms in seconds is calculated with the
formula:
t s
deadband
Y
( )
(max min) /
%
=
− ×
×
1000
100∆
GUID-5381484E-E205-4548-A846-D3519578384B V1 EN (Equation 82)
Example for CMMXU:
A deadband = 2500 (2.5% of the total measuring range of 40)
I_INST_A = I_DB_A = 0.30
If I_INST_A changes to 0.40, the reporting delay is:
t s s( )
( ) /
. . %
=
− ×
− ×
=
40 0 2500 1000
0 40 0 30 100
10
GUID-D1C387B1-4F2E-4A28-AFEA-431687DDF9FE V1 EN
Table 533: Parameters for deadband calculation
Function
Settings Maximum/minimum (=range)
Three-phase current
measurement (CMMXU)
A deadband 40 / 0 (=40xIn)
Three-phase voltage
measurement (VMMXU)
V Deadband 4 / 0 (=4xUn)
Residual current measurement
(RESCMMXU)
A deadband res 40 / 0 (=40xIn)
Residual voltage measurement
(RESVMMXU)
V deadband res 4 / 0 (=4xUn)
Table continues on next page
Section 8 1YHT530004D05 D
Measurement functions
630 615 series
Technical Manual