A070789 V1 EN
Figure 7: Output contact
The internal fault code indicates the type of internal IED fault. When a fault
appears, the code must be recorded so that it can be reported to ABB customer service.
Table 37: Internal fault indications and codes
Fault indication Fault code Additional information
Internal Fault
System error
2 An internal system error has occurred.
Internal Fault
File system error
7 A file system error has occurred.
Internal Fault
Test
8 Internal fault test activated manually by
the user.
Internal Fault
SW watchdog error
10 Watchdog reset has occurred too many
times within an hour.
Internal Fault
SO-relay(s),X100
43 Faulty Signal Output relay(s) in card
located in slot X100.
Internal Fault
SO-relay(s),X110
44 Faulty Signal Output relay(s) in card
located in slot X110.
Internal Fault
SO-relay(s),X120
45 Faulty Signal Output relay(s) in card
located in slot X120.
Internal Fault
SO-relay(s),X130
46 Faulty Signal Output relay(s) in card
located in slot X130.
Internal Fault
PO-relay(s),X100
53 Faulty Power Output relay(s) in card
located in slot X100.
Internal Fault
PO-relay(s),X110
54 Faulty Power Output relay(s) in card
located in slot X110.
Internal Fault
PO-relay(s),X120
55 Faulty Power Output relay(s) in card
located in slot X120.
Internal Fault
PO-relay(s),X130
56 Faulty Power Output relay(s) in card
located in slot X130.
Internal Fault
Light sensor error
57 Faulty ARC light sensor input(s).
Internal Fault
Conf. error,X000
62 Card in slot X000 is wrong type.
Internal Fault
Conf. error,X100
63 Card in slot X100 is wrong type or does
not belong to the original composition.
Table continues on next page