The outputs OK, WARNING and ALARM are extracted from the enumerated input
value. Only one of the outputs can be active at a time. In case the
GOOSERCV_ENUM function block doesn't receive the value from the sending
IED, the default value (0) is used and the ALARM is activated in the T_HEALTH
function block.
3.13.4.3 Signals
Table 81: T_HEALTH Input signals
Name Type Default Description
IN Any 0 Input signal
Table 82: T_HEALTH Output signals
Name Type Description
OK BOOLEAN Output signal
WARNING BOOLEAN Output signal
ALARM BOOLEAN Output signal
3.13.5 T_F32_INT8 function block
3.13.5.1 Function block
GUID-F0F44FBF-FB56-4BC2-B421-F1A7924E6B8C V1 EN
Figure 41: Function block
3.13.5.2 Functionality
T_F32_INT8 is a type conversion function.
The function converts 32-bit floating type values to 8-bit integer type. The
rounding operation is included. Output value saturates if the input value is below
the minimum or above the maximum value.
3.13.5.3 Signals
Table 83: T_F32_INT8 Input signals
Name
Type Default Description
F32 FLOAT32 0.0 Input signal
Section 3 1YHT530004D05 D
Basic functions
106 615 series
Technical Manual