Table 52: Settings for X130 (RTD) analog input limit value supervision
Function Settings for limit value supervision
X130 (RTD) analog input Out of range Value maximum
High-high limit Val high high limit
High limit Val high limit
Low limit Val low limit
Low-low limit Val low low limit
Out of range Value minimum
When the measured value exceeds either the Value maximum setting or the Value
minimum setting, the corresponding quality is set to out of range and a maximum
or minimum value is shown when the measured value exceeds the added
hysteresis, respectively. The hysteresis is added to the extreme value of the range
limit to allow the measurement slightly to exceed the limit value before it is
considered as out of range.
3.11.2.8 Deadband supervision
Each input has an independent deadband supervision. The deadband supervision
function reports the measured value according to integrated changes over a time
period.
GUID-63CA9A0F-24D8-4BA8-A667-88632DF53284 V1 EN
Figure 26: Integral deadband supervision
The deadband value used in the integral calculation is configured with the Value
deadband setting. The value represents the percentage of the difference between
the maximum and minimum limits in the units of 0.001 percent * seconds. The
reporting delay of the integral algorithms in seconds is calculated with the formula:
t s
Y
( )
(
=
×
∆ ×
Value maximum - Value minimum) deadband / 1000
1000%
GUID-CC447162-C1B4-4E74-A253-828F388266EB V1 EN (Equation )
Section 3 1YHT530004D05 D
Basic functions