8.1.7.2 Function block
A070779 V2 EN
Figure 348: Function block
8.1.7.3 Signals
Table 552: RESVMMXU Input signals
Name Type Default Description
Uo SIGNAL 0 Residual voltage
BLOCK BOOLEAN 0=False Block signal for all binary outputs
Table 553: RESVMMXU Output signals
Name Type Description
HIGH_ALARM BOOLEAN High alarm
HIGH_WARN BOOLEAN High warning
8.1.7.4 Settings
Table 554: RESVMMXU Non group settings
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Measurement mode 1=RMS
2=DFT
2=DFT Selects used measurement mode
V Hi high limit res 0.00...4.00 xUn 0.20 High alarm voltage limit
V high limit res 0.00...4.00 xUn 0.05 High warning voltage limit
V deadband res 100...100000 10000 Deadband configuration value for
integral calculation. (percentage of
difference between min and max as
0,001 % s)
8.1.7.5 Monitored data
Table 555: RESVMMXU Monitored data
Name
Type Values (Range) Unit Description
Uo-kV FLOAT32 0.00...4.00 xUn Measured residual
voltage
Section 8 1YHT530004D05 D
Measurement functions
640 615 series
Technical Manual