Table 397: PHPTUV Non group settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Num of start phases 1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases required for operate
activation
Minimum operate time 60...60000 ms 1 60 Minimum operate time for IDMT curves
Reset delay time 0...60000 ms 1 20 Reset delay time
Curve parameter A 0.005...200.000 1.000 Parameter A for customer programmable
curve
Curve parameter B 0.50...100.00 1.00 Parameter B for customer programmable
curve
Curve parameter C 0.0...1.0 0.0 Parameter C for customer
programmable curve
Curve parameter D 0.000...60.000 0.000 Parameter D for customer
programmable curve
Curve parameter E 0.000...3.000 1.000 Parameter E for customer programmable
curve
Curve Sat Relative 0.0...3.0 0.1 2.0 Tuning parameter to avoid curve
discontinuities
Voltage block value 0.05...1.00 xUn 0.01 0.20 Low level blocking for undervoltage mode
Enable block value 0=False
1=True
1=True Enable internal blocking
Voltage selection 1=phase-to-earth
2=phase-to-phase
2=phase-to-phase Parameter to select phase or phase-to-
phase voltages
Relative hysteresis 1.0...5.0 % 0.1 4.0 Relative hysteresis for operation
4.5.2.9 Monitored data
Table 398: PHPTUV Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
PHPTUV Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Section 4 1YHT530004D05 D
Protection functions
480 615 series
Technical Manual