Name Type Values (Range) Unit Description
DIR_A Enum 0=unknown
1=forward
2=backward
3=both
Direction phase A
DIR_B Enum 0=unknown
1=forward
2=backward
3=both
Direction phase B
DIR_C Enum 0=unknown
1=forward
2=backward
3=both
Direction phase C
ANGLE_A FLOAT32 -180.00...180.00 deg Calculated angle
difference, Phase A
ANGLE_B FLOAT32 -180.00...180.00 deg Calculated angle
difference, Phase B
ANGLE_C FLOAT32 -180.00...180.00 deg Calculated angle
difference, Phase C
DPHHPDOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.1.3.11 Technical data
Table 209: DPHxPDOC Technical data
Characteristic
Value
Operation accuracy Depending on the frequency of the current/
voltage measured: f
n
±2 Hz
DPHLPDOC
Current:
±1.5% of the set value or ±0.002 x I
n
Voltage:
±1.5% of the set value or ±0.002 x U
n
Phase angle: ±2°
DPHHPDOC Current:
±1.5% of the set value or ±0.002 x I
n
(at currents in the range of 0.1…10 x I
n
)
±5.0% of the set value
(at currents in the range of 10…40 x I
n
)
Voltage:
±1.5% of the set value or ±0.002 x U
n
Phase angle: ±2°
Start time
1)2)
Minimum Typical Maximum
I
Fault
= 2.0 x set
Start
value
38 ms 43 ms 46 ms
Reset time < 40 ms
Reset ratio Typical 0.96
Retardation time < 35 ms
Table continues on next page
1YHT530004D05 D Section 4
Protection functions
615 series 199
Technical Manual