10.3.9 Monitored data
Table 657: PHQVVR Monitored data
Name Type Values (Range) Unit Description
ST_A BOOLEAN 0=False
1=True
Start Phase A (Voltage
Variation Event in
progress)
ST_B BOOLEAN 0=False
1=True
Start Phase B (Voltage
Variation Event in
progress)
ST_C BOOLEAN 0=False
1=True
Start Phase C (Voltage
Variation Event in
progress)
INSTSWELLCNT INT32 0...2147483647 Instantaneous swell
operation counter
MOMSWELLCNT INT32 0...2147483647 Momentary swell
operation counter
TEMPSWELLCNT INT32 0...2147483647 Temporary swell
operation counter
MAXDURSWELLCN
T
INT32 0...2147483647 Maximum duration swell
operation counter
INSTDIPCNT INT32 0...2147483647 Instantaneous dip
operation counter
MOMDIPCNT INT32 0...2147483647 Momentary dip operation
counter
TEMPDIPCNT INT32 0...2147483647 Temporary dip operation
counter
MAXDURDIPCNT INT32 0...2147483647 Maximum duration dip
operation counter
MOMINTCNT INT32 0...2147483647 Momentary interruption
operation counter
TEMPINTCNT INT32 0...2147483647 Temporary interruption
operation counter
SUSTINTCNT INT32 0...2147483647 Sustained interruption
operation counter
MAXDURINTCNT INT32 0...2147483647 Maximum duration
interruption operation
counter
PHQVVR Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Time Timestamp Time
Variation type Enum 0=No variation
1=Swell
2=Dip
3=Swell + dip
4=Interruption
5=Swell + Int
6=Dip + Int
7=Swell+dip+Int
Variation type
Table continues on next page
1YHT530004D05 D Section 10
Power quality measurement functions
615 series 787