4.2.4.8 Settings
Table 319: EFPADM Group settings
Parameter Values (Range) Unit Step Default Description
Voltage start value 0.01...2.00 xUn 0.01 0.15 Voltage start value
Directional mode 1=Non-directional
2=Forward
3=Reverse
2=Forward Directional mode
Operation mode 1=Yo
2=Go
3=Bo
4=Yo, Go
5=Yo, Bo
6=Go, Bo
7=Yo, Go, Bo
1=Yo Operation criteria
Operate delay time 60...200000 ms 10 60 Operate delay time
Circle radius 0.05...500.00 mS 0.01 1.00 Admittance circle radius
Circle conductance -500.00...500.00 mS 0.01 0.00 Admittance circle midpoint, conductance
Circle susceptance -500.00...500.00 mS 0.01 0.00 Admittance circle midpoint, susceptance
Conductance forward -500.00...500.00 mS 0.01 1.00 Conductance threshold in forward
direction
Conductance reverse -500.00...500.00 mS 0.01 -1.00 Conductance threshold in reverse
direction
Conductance tilt Ang -30...30 deg 1 0 Tilt angle of conductance boundary line
Susceptance forward -500.00...500.00 mS 0.01 1.00 Susceptance threshold in forward
direction
Susceptance reverse -500.00...500.00 mS 0.01 -1.00 Susceptance threshold in reverse
direction
Susceptance tilt Ang -30...30 deg 1 0 Tilt angle of susceptance boundary line
Table 320: EFPADM Non group settings
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Admittance Clc mode 1=Normal
2=Delta
1=Normal Admittance calculation mode
Reset delay time 0...60000 ms 1 20 Reset delay time
Pol reversal 0=False
1=True
0=False Rotate polarizing quantity
Min operate current 0.01...1.00 xIn 0.01 0.01 Minimum operating current
Min operate voltage 0.01...1.00 xUn 0.01 0.01 Minimum operating voltage
Io signal Sel 1=Measured Io
2=Calculated Io
1=Measured Io Selection for used Io signal
Uo signal Sel 1=Measured Uo
2=Calculated Uo
1=Measured Uo Selection for used Uo signal