8.3.6 Signals
Table 582: TPOSSLTC Input signals
Name Type Default Description
BI0 BOOLEAN 0=False Binary input 1
BI1 BOOLEAN 0=False Binary input 2
BI2 BOOLEAN 0=False Binary input 3
BI3 BOOLEAN 0=False Binary input 4
BI4 BOOLEAN 0=False Binary input 5
BI5 BOOLEAN 0=False Binary input 6
SIGN_BIT BOOLEAN 0=False Binary input sign bit
TAP_POS INT8 0 Tap position indication
8.3.7 Settings
Table 583: TPOSSLTC Non group settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Operation mode 1=NAT2INT
2=BCD2INT
3=GRAY2INT
2=BCD2INT Operation mode selection
8.3.8 Monitored data
8.3.9 Technical data
Table 584: TPOSSLTC Technical data
Descrpition
Value
Response time for binary inputs Typical 100 ms
8.3.10 Technical revision history
Table 585: TPOSSLTC Technical revision history
Technical revision
Change
B Added new input TAP_POS
1YHT530004D05 D Section 8
Measurement functions
615 series 665
Technical Manual

Table of Contents

Related product manuals