Not allowed: no automatic initiation is allowed
When the synchronization fails, the automatic initiation is carried out when the
auto wait time elapses and the reclosing is prevented due to a failure during the
synchronism check
When the circuit breaker does not close, the automatic initiation is carried out
if the circuit breaker does not close within the wait close time after issuing the
reclose command
Both: the automatic initiation is allowed when synchronization fails or the
circuit breaker does not close.
The Auto init parameter defines which INIT_X lines are activated
in the auto-initiation. The default value for this parameter is "0",
which means that no auto-initiation is selected.
A070871 V1 EN
Figure 381: Example of an auto-initiation sequence with synchronization failure
in the first shot and circuit breaker closing failure in the second shot
In the first shot, the synchronization condition is not fulfilled (SYNC is FALSE).
When the auto wait timer elapses, the sequence continues to the second shot.
During the second reclosing, the synchronization condition is fulfilled and the close
command is given to the circuit breaker after the second reclose time has elapsed.
After the second shot, the circuit breaker fails to close when the wait close time has
elapsed. The third shot is started and a new close command is given after the third
reclose time has elapsed. The circuit breaker closes normally and the reclaim time
starts. When the reclaim time has elapsed, the sequence is concluded successful.
9.4.4.3 Shot pointer controller
The execution of a reclose sequence is controlled by a shot pointer. It can be
adjusted with the SHOT_PTR monitored data.
The shot pointer starts from an initial value "1" and determines according to the
settings whether or not a certain shot is allowed to be initiated. After every shot,
Section 9 1YHT530004D05 D
Control functions
702 615 series
Technical Manual