Table 599: ESXSWI Monitored data
Name Type Values (Range) Unit Description
POSITION Dbpos 0=intermediate
1=open
2=closed
3=faulty
Apparatus position
indication
9.1.9 Technical revision history
Table 600: CBXCBR Technical revision history
Technical revision Change
B Interlocking bypass input (ITL_BYPASS) and
opening enabled (OPEN_ENAD)/closing enabled
(CLOSE_ENAD) outputs added. ITL_BYPASS
bypasses the ENA_OPEN and ENA_CLOSE states.
9.2 Disconnector position indicator DCSXSWI and
earthing switch indication ESSXSWI
9.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Disconnector position indicator DCSXSWI I<->O DC I<->O DC
Earthing switch indication ESSXSWI I<->O ES I<->O ES
9.2.2 Function block
A071280 V2 EN
Figure 360: Function block
A071282 V2 EN
Figure 361: Function block
Section 9 1YHT530004D05 D
Control functions
676 615 series
Technical Manual