GUID-CD0B7D5A-1F1A-47E6-AF2A-F6F898645640 V2 EN
Figure 88: Configurable operating sectors
Table 194: Momentary per phase direction value for monitored data view
Criterion for per phase direction information
The value for DIR_A/_B/_C
The ANGLE_X is not in any of the defined
sectors, or the direction cannot be defined due
too low amplitude
0 = unknown
The ANGLE_X is in the forward sector 1 = forward
The ANGLE_X is in the reverse sector 2 = backward
(The ANGLE_X is in both forward and reverse
sectors, that is, when the sectors are overlapping)
3 = both
Table 195: Momentary phase combined direction value for monitored data view
Criterion for phase combined direction information
The value for DIRECTION
The direction information (DIR_X) for all phases
is unknown
0 = unknown
The direction information (DIR_X) for at least one
phase is forward, none being in reverse
1 = forward
The direction information (DIR_X) for at least one
phase is reverse, none being in forward
2 = backward
The direction information (DIR_X) for some
phase is forward and for some phase is reverse
3 = both