If a warning appears, record the name and code so that it can be
provided to ABB customer service.
Table 38: Warning indications and codes
Warning indication Warning code Additional information
Warning
Watchdog reset
10 A watchdog reset has occurred.
Warning
Power down det.
11 The auxiliary supply voltage has dropped
too low.
Warning
IEC61850 error
20 Error when building the IEC 61850 data
model.
Warning
Modbus error
21 Error in the Modbus communication.
Warning
Dataset error
24 Error in the Data set(s).
Warning
Report cont. error
25 Error in the Report control block(s).
Warning
GOOSE contr. error
26 Error in the GOOSE control block(s).
Warning
SCL config error
27 Error in the SCL configuration file or the
file is missing.
Warning
Logic error
28 Too many connections in the
configuration.
Warning
SMT logic error
29 Error in the SMT connections.
Warning
GOOSE input error
30 Error in the GOOSE connections.
ACT error 31 Error in the ACT connections.
Warning
GOOSE Rx. error
32 Error in the GOOSE message receiving.
Warning
AFL error
33 Analog channel configuration error.
Warning
Unack card comp.
40 A new composition has not been
acknowledged/accepted.
Warning
Protection comm.
50 Error in protection communication.
Warning
ARC1 cont. light
85 A continuous light has been detected on
the ARC light input 1.
Warning
ARC2 cont. light
86 A continuous light has been detected on
the ARC light input 2.
Warning
ARC3 cont. light
87 A continuous light has been detected on
the ARC light input 3.
Warning
RTD card error,X130
96 Temporary error occurred in RTD card
located in slot X130.
Warning
RTD meas. error,X130
106 Measurement error in RTD card located
in slot X130.
Section 3 1YHT530004D05 D
Basic functions
62 615 series
Technical Manual

Table of Contents

Related product manuals