Binary input/output module, mA and time synchronization boards. #10 Notes and Rules
Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability
is further increased.
BIM with 30 mA inrush current is still available.
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1BIM and 1 BOM included.
Slot position (rear view)
X31
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
Note: Max 3 positions in 1/2 rack, 5
in 3/4 rack with 2 TRM and 11 in
1/1 rack with 2 TRM
1/2 Case with 1 TRM █ █ █ Note: Only for A10/A25/A30
3/4 Case with 2 TRM █ █ █ █ █
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █
No board in slot X X X X X X X X X X X
Binary output module 24 output relays (BOM) A A A A A A A A A A Note: Maximum 4 (BOM+SOM
+MIM) boards. Only 1 BOM in A10
BIM 16 inputs, RL24-30 VDC, 50 mA B
1
B
1
B
1
B
1
B
1
B
1
B
1
B
1
B
1
B
1
Note: Only 1 BIM in A10
BIM 16 inputs, RL48-60 VDC, 50 mA C
1
C
1
C
1
C
1
C
1
C
1
C
1
C
1
C
1
C
1
BIM 16 inputs, RL110-125 VDC, 50 mA D
1
D
1
D
1
D
1
D
1
D
1
D
1
D
1
D
1
D
1
BIM 16 inputs, RL220-250 VDC, 50 mA E
1
E
1
E
1
E
1
E
1
E
1
E
1
E
1
E
1
E
1
BIM 16 inputs, 220-250 VDC, 120mA E
2
E
2
E
2
E
2
E
2
E
2
E
2
E
2
E
2
E
2
BIMp 16 inputs, RL24-30 VDC, 30 mA, for pulse counting F F F F F F F F F
BIMp 16 inputs, RL48-60 VDC, 30 mA, for pulse counting G G G G G G G G G
BIMp 16 inputs, RL110-125 VDC, 30 mA, for pulse counting H H H H H H H H H
BIM 16 inputs, RL220-250 VDC, 30 mA, for pulse counting K K K K K K K K K
IOM 8 inputs, 10+2 output, RL24-30 VDC, 50 mA L1 L1 L1 L1 L1 L1 L1 L1 L1
IOM 8 inputs, 10+2 output, RL48-60 VDC, 50 mA M
1
M
1
M
1
M
1
M
1
M
1
M
1
M
1
M
1
IOM 8 inputs, 10+2 output, RL110-125 VDC, 50 mA N
1
N
1
N
1
N
1
N
1
N
1
N
1
N
1
N
1
IOM 8 inputs, 10+2 output, RL220-250 VDC, 50 mA P
1
P
1
P
1
P
1
P
1
P
1
P
1
P
1
P
1
IOM 8 inputs 10+2 output relays, 220-250 VDC, 110mA P
2
P
2
P
2
P
2
P
2
P
2
P
2
P
2
P
2
IOM with MOV 8 inputs, 10-2 output, 24-30 VDC, 30 mA U U U U U U U U U
IOM with MOV 8 inputs, 10-2 output, 48-60 VDC, 30 mA V V V V V V V V V
IOM with MOV 8 inputs, 10-2 output, 110-125 VDC, 30 mA W W W W W W W W W
IOM with MOV 8 inputs, 10-2 output, 220-250 VDC, 30 mA Y Y Y Y Y Y Y Y Y
mA input module MIM 6 channels R R R R R R R R R Note: Maximum 1 MIM board in
1/2 case
SOM Static output module, 12 outputs, 48-60 VDC T1 T1 T1 T1 T1 T1 T1 T1 T1 Rule: SOM must not to be placed
in position nearest NUM 1/2 case
slot P5 3/4 case, 1 TRM slot P10
3/4 case, 2 TRM slot P7 1/1 case,
1 TRM slot P16 1/1 case, 2 TRM
slot P13
SOM static outputs module, 12 outputs, 110-250 VDC T2 T2 T2 T2 T2 T2 T2 T2 T2
Selection for position #10.
Transformer protection RET670 2.0
1MRK 504 141-BEN C
Product version: 2.0