Maintenance Operating Mechanism Maintenance
16 1HSB515409-100 en rev2
4.7 Drive unit
Check and clean the shafts in the catch gear and the worm gears in the drive
unit.
Lubricate these with Grease “M” at intervals of 3-6 years or 2,000 operations.
Measure the motor current at the end of the spring charging procedure at
intervals of 15 years or 5,000 operations. See the relevant Assembly
Instructions for the circuit-breaker, chapter Operating values.
The motor should be capable of charging the springs at 85% of its nominal voltage
(IEC).
Figure 4-7. Drive unit
4.7.1 Switch Hand-Motor
Check that the signal for voltage failure functions. If not, replace the switch.