EasyManua.ls Logo

ABB SF6 LTB 245E1 BLG 1002A - 5 Dismantling the Circuit-Breaker Pole; Dismantling the Tripping Mechanisms Pull-Rod

ABB SF6 LTB 245E1 BLG 1002A
231 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Overhaul Instructions
Dismantling the circuit-breaker pole
1HSB435409-201 enrev1 13
5. Dismantling the circuit-breaker pole
The circuit-breaker pole is fitted vertically on an appropriate frame, for example, a
circuit-breaker frame or a frame on the floor of the workshop.
5.1 Dismantling the tripping mechanism’s pull-rod
1. Dismantle the protective cover (8).
2. Measure and note down a reference dimension, e.g. “Y”, so that the opening
spring (5) can be refitted to the same tension using the nut (6) when re-
assembling.
Y=............. mm date................
3. Off-load the springs by loosening the nuts (6, 7)
4. Remove the pin (2).
Figure 5-1. Dismantling the pull-rod.
Item
1 Operating lever
2 Pin
3 Pull-rod
4 Spring housing
5 Opening spring
6 Nut
7 Locking nut
8 Protective cover
9 Bolts M10x25 4 pcs.
Y
7
2
1
3
4
5
6
B10056
9
8

Table of Contents