 Chapter 6 - Operation
UNITROL 1020 User Manual 3BHS335648 E82 145
PSS Test Interface
a. The operator switches on/off PSS input signals and injections points
b. The operator selects two test points from the range TP1 TP16
Both selected signals are shown in the CMT1000 Oscilloscope and are routed to the
analog output
c. The operator adjusts the analog output amplitude
l-shift (0 to 7) is equal to a factor of 2
(I-sift)
Eg. If l-shift equals 2, the analog output is multiplied by factor 4
Scaling of TP can be seen in the table below.
The analog output range can be configured with min (-10V to +10V) and max (-10V to +10V) values
which represent the scaling. All values represent peak values.
TP
Signal Name
Scaling
I-shift
1
Frequency meausurement input
±12.5%
0
2
Frequency washout input
±12.5%
0
3
Frequency washout output
±12.5%
0
4
Ramp Track filter output
±25.0%
1
5
Power Input
±200%
4
6
Power washout input
±200%
4
7
Delta Power integrator output
±25.0%
1
8
Lead lag input
±25.0%
1
9
Lead lag output
±25.0%
1
10
Lead lag output limited
±25.0%
1
11
PID output
±100.0%
3
12
PID output limited
±50.0%
2