Introduction – RS485 interfaces |
9
RS485 interfaces
There are two RS485 interfaces on the top of the eMShome (
A
and
B
) which are used for communication with the
eMH1 Wallboxes. The following specifications apply to the RS485 interfaces:
Requirement for the data cable
Nominal voltage/wire insulation: 300V RMS
Cable cross section: 0.25–1.5mm²
Cable type: rigid or flexible
Recommendation: To do this, please refer to the section on “Data cable recommendations” onpage49.
Requirement for cable installation
In the area for connecting the RS485 interfaces on the eMShome, mechanical means must be provided to ensure
that individual wires of the connecting cable are at least 10mm away from live parts.
The connecting cable must be run separately from the mains cables in the distribution board and on the perma-
nent link.
Connection diagram for RS485 connector
Pin Identification Description
1
A
1
B
VCC Voltage output for supply of external devices, 9 V ± 10%, max. 280mA
2
A
2
B
GND Ground
3
A
3
B
A RS485A
4
A
4
B
B RS485B
A
B
4
3
2
1
4
3
2
1