101
retrieving partial data. Waveform Group Number for Retrieving (8E00H) will stop
increasing while value reaches Newest Waveform Group Number. If the value
added 4, the value will be larger than Newest Waveform Group Number.
Second retrieving method is retrieving all waveforms data. When 0x8E01H
(Waveform Group Number) is set to 1~121, each time only one group data of
each number will be retrieved, then Waveform Group Number for Retrieving
(8E01H) will automatically add 1 after retrieving. At next time, new Waveform
Group Number will be retrieved. Waveform Group Number will stop increasing
after value reach 121.
Note: The range of 0x8E01H is 0~121, within setting range, windows
(8E04H~8E43H) are corresponding to waveform data.
0: Only retrieving waveform record reasons
1: Time and reasons of waveforms
2~11: Each waveform number of ten waveforms before U1 waveform is
triggered
12~21: Each waveform number of ten waveforms before U2 waveform is
triggered
22~31: Each waveform number of ten waveforms before U3 waveform is
triggered
32~41: Each waveform number of ten waveforms before I1 waveform is
triggered
42~51: Each waveform number of ten waveforms before I2 waveform is
triggered
52~61: Each waveform number of ten waveforms before I3 waveform is
triggered
62~71: Each waveform number of ten waveforms after U1 waveform is triggered

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AccuEnergy Acuvim II series and is the answer not in the manual?

AccuEnergy Acuvim II series Specifications

General IconGeneral
BrandAccuEnergy
ModelAcuvim II series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals