218
i). Set BACnet/IP port in the seventh setting page, such as 47808. Press the "V/
A" key to go to the setting page. Users may set the parameters pointed out in
Fig 5-83. The cursor starts at the rst digit. The BACnet/IP ports default value is
47808, and the user dened range of port is 1~65535. After setting the BACnet/
IP port, press the "V/A" key to accept. Press the "P" key to go to the eighth
setting page for the BACnet RESET.
Fig 5-76
j). Set resetting mode in the eighth setting page. Select “RESET to reset the
module. Selecting “NO” will not reset the module. Press the "V/A" key to go to
the setting page and the parameter pointed out in Fig 5-84 will ash.Press the
"P" or "E" key to select the conguration mode. Press the "V/A" key to accept.
Note: When conguring BACnet module settings completely, users must select
“RESET to restart module and new settings will take eect.