4.7 Process Monitor Operation
Process Monitor operation will initiate the following events:
The piezo sounder pulses ¼ second On and ¼ second Off
The LCD displays a process monitor message along with the device name, type,
address, adjective/noun, associated zones and time/date
Relays programmed for process monitoring will be activated
The alarm relay is not
activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Note that, like supervisories, process monitor signals latch (except when programmed for
process monitor autoresettable) and can be assigned to software zones.
4.8 Hazard Condition Operation
Hazard Condition operation will initiate the following events:
The piezo sounder turns on steady
The LCD displays a hazard message along with the device name, type, address,
adjective/noun, associated zones and time/date
Relays programmed for process monitoring will be activated
The alarm relay is not
activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Hazard conditions do not latch and will therefore clear when the hazard condition is
cleared. They can be assigned to software zones.
4.9 Medical Alert Condition Operation
Medical Alert Condition operation will initiate the following events:
The piezo sounder turns on steady
The LCD displays a medical alert message along with the device name, type,
address, adjective/noun, associated zones and time/date
Relays programmed for medical alert will be activated
The alarm relay is not
activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Medical alert conditions do not latch and will therefore clear when the medical alert
condition is cleared. They can be assigned to software zones.
4.10 NAC Operation
There are two programmable NACs (Notification Appliance Circuits) resident on the
Unimode 9600 main circuit board. Both NACs may be programmed as silenceable or
nonsilenceable and may also be programmed for steady or coded operation. Coded
operation provides a choice between March Time, Temporal or California coding.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ADT Unimode 9600 and is the answer not in the manual?

ADT Unimode 9600 Specifications

General IconGeneral
BrandADT
ModelUnimode 9600
CategoryControl Panel
LanguageEnglish

Related product manuals