INSPY. 1003. 4138305_03
42
14.5. SOUND LEVELS AT FULL LOAD
STANDARD NS E
WITH THE KIT
ACCESSORY AK, (L/E)
(can only be installed when the machine
is being built and must therefore be
specified in the order) there is a further
noise reduction, see next data table.
NB
For further information to the KIT, refer to
the chapter ACCESSORIES
The nominal value refers to:
Evaporator water temperature .......12/7 °C
Condenser air temperature ................. 35°C
∆t ................................................................ 5°C
NS
Total sound levels Octave band[Hz]
Pow.
dB(A)
Pressure 125 250 500 1000 2000 4000 8000
dB(A)
10m
dB(A)
1m
Sound power by central band frequency [dB]
1251 84 51,8 64,3 80.8 80.5 79.6 81.2 75.8 66.6 53.7
1401 83 50,8 63,3 80.8 80.5 79.1 80.2 74.8 65.6 53.7
1601 84 51,8 64,3 80.8 80.5 80.6 81.7 74.3 64.6 53.7
1801 85 52,6 64,8 88.4 83.7 82.7 79.6 74.2 72.1 59.6
2101 86 53,5 65,4 87.5 86.4 82.6 82.3 76.0 69.4 57.7
2401 86 53,5 65,4 87.5 87.4 82.1 82.3 76.0 70.4 58.7
1402 83 50,8 63,3 83.3 81.9 80.7 77.5 74.5 66.5 54.6
1602 84 51,8 64,3 83.2 80.9 83.3 80.0 73.5 66.5 54.6
1802 84 51,6 63,8 82.3 79.9 81.8 81.7 71.5 64.0 53.6
2002 85 52,5 64,4 82.9 81.3 82.0 82.6 73.9 65.3 52.5
2202 85 52,5 64,4 82.5 80.7 80.7 82.6 75.9 64.6 52.3
2352 85 52,5 64,4 82.5 80.7 80.7 82.6 75.9 64.6 52.3
2502 85 52,5 64,4 82.5 80.7 80.7 82.6 75.9 64.6 52.3
2652 85 52,5 64,4 82.5 80.7 80.7 82.6 75.9 64.6 52.3
2802 86 53,5 65,4 82.5 81.7 82.2 83.6 76.4 65.6 53.3
3002 86 53,4 64,8 82.5 81.7 82.2 83.6 76.4 65.6 53.3
3202 86 53,4 64,8 82.5 81.7 82.2 83.6 76.4 65.6 53.3
3402 87 54,3 65,5 88.3 86.3 84.6 83.5 78.1 69.6 56.8
3602 87 54,2 65,2 92.1 88.0 84.9 81.5 75.8 71.6 59.3
3902 87 54,1 64,9 91.1 88.3 84.6 82.6 75.7 70.0 57.3
4202 88 55,1 65,9 89.2 88.1 84.3 84.7 78.1 70.4 57.3
4502 88 55,0 65,6 89.2 88.1 84.3 84.7 78.1 70.4 57.3
4802 88 55,0 65,6 89.2 88.1 84.3 84.7 78.1 70.4 57.3
5002 89 56,0 66,6 90.6 87.7 85.5 85.5 79.8 71.3 58.7
5202 89 56,0 66,6 92.5 88.8 85.7 84.7 78.4 71.3 58.6
5402 88 55,0 65,6 94.2 88.5 86.5 83.4 78.0 74.4 62.4
5702 89 56,0 66,6 93.0 89.7 86.0 85.2 78.7 72.0 60.5
6003 89 55,6 65,7 93.0 89.7 86.0 85.2 78.7 72.5 59.5
6303 89 55,5 65,5 91.0 88.4 85.6 85.8 79.1 73.2 60.5
6603 90 56,5 66,5 93.0 91.2 86.6 86.4 79.5 72.0 60.5
6903 91 57,4 67,3 93.1 91.8 87.3 87.9 80.3 71.9 60.5
7203 92 58,4 68,3 93.6 93.8 87.8 88.4 82.3 73.9 60.5
15. SAFETY AND CHECK PARAMETER SETTING
CHECK PARAMETERS
Cold Setting
Water inlet temperature in cooling mode
MIN.
4°C
MAX.
15°C
DEFAULT
7.0°C
Antifreeze intervention
Antifreeze alarm intervention temperature on EV side (water
output temperature).
MIN.
-9°C
MAX.
4°C
DEFAULT
3°C
Total differential
Proportional temperature band within which the compressors are
activated and deactivated
MIN.
3°C
MAX.
10°C
DEFAULT
5°C
Autostart Auto