Dip-switch No. dip Status Function
A
1
ON Machine set as heat pump
OFF Machine set for cooling only
2
ON Defrosting only by cycle reversal
OFF Defrosting by hot gas injection
3
ON Glycol water: anti-freeze setting can be modified
OFF Anti-freeze setting (parameter B) blocked
4
ON Output control deactivated
OFF Output control activated
5
ON Safety capacity controls deactivated
OFF Safety capacity controls activated
6
ON Algorithm for check of low water content deactivated
OFF Algorithm for check of low water content activated
7
ON Condensation pressure control device present (accessory DCP)
OFF Condensation pressure control device absent (accessory DCP)
8
ON Configuration of the card for ANR unit (R407C)
OFF Configuration of the card for ANL unit (R410A)
9
ON Configuration of the card for inverter unit
OFF Configuration of the card for ON/OFF chiller unit
10
ON Configuration of the card for condenser unit
OFF Configuration of the card for chiller unit
11
ON Not used
OFF Not used
12
ON Not used
OFF Not used
Dip-switch
Dip combinations
Function
DIP 1 DIP 2
B
OFF OFF Factory settings
ON OFF Factory settings
ON ON Factory settings
OFF ON Factory settings