EasyManua.ls Logo

AERMEC TRS Series - Page 68

AERMEC TRS Series
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
68
TRS
24/07 5979398_00
is higher than setting value, the unit will work at the maximum air ow rate; if the unit is already in highest speed when CO
2
concentration higher than setting value, then unit keeps the highest speed running. If concentration reduces lower than
setting value, then unit returns back to the previous status (standby, speed 1, 2, 3 etc.).
WARNING: the unit keeps ON as long as the concentration value will not drop under the set, even though the unit is
switched OFF by the controller.
Humidity sensor - TRSUSW
The humidity sensor comes complete with a 5 metre long cable and connectors for connection to the electronic board on
the machine. If necessary, a longer cable can be used to load the installer (max. 15 metres overall, cable specication AWM
2464 24AWG VW-1 80°C 300V 4-pole). . See dedicated chapter For details of the connection to the electronic card.
If humidity is higher than setting value, the unit will work at the maximum air ow rate; if the unit is already in highest speed
when the humidity level is higher than setting value, then unit keeps the highest speed running. If humidity level reduces
lower than setting value, then unit returns back to the previous status (standby, speed 1, 2, 3 etc.).
WARNING: the unit keeps ON as long as the humidity level will not drop under the set, even though the unit is
switched OFF by the controller.

Table of Contents

Related product manuals