102 Rockwell Automation Publication 825-UM004D-EN-P - November 2012
Chapter 6 Configuring Protection & Logic Functions
The relay asserts the Emergency Restart bit in response to any of the following
conditions:
the control input assigned to Emergency Restart asserts.
the relay receives a network Emergency Restart control command.
When
the Emergency Restart bit asserts, the relay does the following:
Resets the motor thermal element capacity used to 0%.
Manipulates the Starts-Per-Hour, Minimum Time Between Starts, and
Ant
i-backspin functions to permit an immediate start.
D
e-asserts the Trip output contact if a fault detecting element is not
pic
ked up.
Initiates a motor start.