EasyManua.ls Logo

Allen-Bradley 825-P - Node Commissioning

Allen-Bradley 825-P
266 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 825-UM004D-EN-P - November 2012 117
825-PDN DeviceNet Communication Card Chapter 9
Figure 40 - Connecting 5-Pin Linear Plug to DeviceNet Cable
Table 52 - Linear Plug Function Descriptions
5. Connect the wired 5-pin linear plug to the 825-PDN DeviceNet
Communication Card, securing with the two screws
Node Commissioning
The 825-PDN DeviceNet Communication Card is shipped with a default
software node address (MAC ID) setting of 63 and the data rate set to Autobaud.
Each device on a DeviceNet network must have a unique node address which can
be set to a value from 0 to 63.
Keep in mind that most DeviceNet systems use address 0 for the master device
(Scanner) and node address 63 should be left vacant for introduction of new slave
devices.
The node address and data rate for the 825-PDN DeviceNet Communication
Card can be changed using software or by setting the hardware switches that
reside on the card. While both methods yield the same result, it is a good practice
to choose one method and deploy it throughout the system.
Terminal Color Signal Function
5RedV+Power Supply
4 White Can_H Signal High
3 Bare SHIELD Shield
2 Blue CAN_L Signal Low
1BlackV-Common

Table of Contents