EasyManua.ls Logo

Allen-Bradley 825-P - Current Imbalance; Phase Loss; Rockwell Automation Publication 825-UM004 D-EN-P - November

Allen-Bradley 825-P
266 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
78 Rockwell Automation Publication 825-UM004D-EN-P - November 2012
Chapter 6 Configuring Protection & Logic Functions
Current Imbalance/
Phase Loss
Imbalanced motor terminal voltages cause imbalanced stator currents to flow in
the motor. The negative-sequence current component of the imbalance current
causes significant rotor heating. While the 825-P motor thermal element models
the heating effect of the negative-sequence current, you could want the additional
imbalance and single-phasing protection offered by a current imbalance element.
The 825-P calculates percent imbalance current in one of two ways, depending
on the magnitude of the average current.
When the average current, Iav, is:
1. greater than the motor-rated full load current, the relay calculates the
percent imbalance:
2. less than the moto
r-rated full load current, the relay calculates the percent
imbalance:
where:
U
B%
= current imbalance percentage
Im = magnitude of phase current with largest deviation from average
Iav = magnitude of the average phase current
FLA = motor-rated full load current
In either case, the function is disabled if the average phase current magnitude is
less than 25% of the Full Load Amps setting.
A 1% voltage imbalance typically causes approximately 6% current imbalance in
induction motors. If a 2% voltage imbalance can occur in your location, set the
current imbalance Warn Level greater than 12% to prevent nuisance alarms. A
15% current imbalance Warn Level setting corresponds to an approximately 2.5%
voltage imbalance, and a 20% current imbalance trip setting corresponds to an
approximately 3.3% voltage imbalance. A 10-second alarm delay and 5-second
trip delay should provide adequate performance in most applications.
Table 19 - Current Imbalance Settings
Setting Prompt Setting Range Factory Default
CI TRIP LEVEL Off, 5…80% Off
CI TRIP DELAY 0…240 s 5
CI WARN LEVEL Off, 5…80% 10
CI WARN DELAY 0…240 s 10
UB% = 100 x
[(Im - Iav)]
Iav
UB% = 100 x
[(Im - Iav)]
FLA

Table of Contents