112 Rockwell Automation Publication 825-UM004D-EN-P - November 2012
Chapter 8 Analyzing Events
Table 50 - Example SER Report Explanations
Item # Explanation
11, 10, 9, 8, 7 After a 10-second accelerating time, the motor relay indicates the motor is running (9).
Later, the ambient temperature alarm element asserts.
6, 5 The ambient temperature trip element times out, causing the relay to trip. Trip
is asserted.
4, 3 Declining temperature allows the elements to drop out.
2, 1 As the current continues to drop, the relay declares the motor stopped.