Rockwell Automation Publication 825-UM004D-EN-P - April 2012 227
Parameter List Chapter B
Current
Data
344 40245 L1 CURRENT 0 65535 — 1 A Get
345 40246 L1 ANGLE -1800 1800 — 10 ° Get
346 40247 L2 CURRENT 0 65535 — 1 A Get
347 40248 L2 ANGLE -1800 1800 — 10 ° Get
348 40249 L3 CURRENT 0 65535 — 1 A Get
349 40250 L3 ANGLE -1800 1800 — 10 ° Get
350 40251 GF CURR (CORE B) 0 65535 — 1 A Get
351 40252 GF-CB ANGLE -1800 1800 — 10 ° Get
352 40253 GF CURR (RESID) 0 65535 — 1 A Get
353 40254 GF-RES ANGLE -1800 1800 — 10 ° Get
354 40255 AVERAGE CURRENT 0 65535 — 1 A Get
355 40256 MOTOR LOAD 0 120 — 10 x Ie Get
356 40257 CURRENT IMBAL 0 1000 — 10 % Get
Voltage
Data
357 40258 VAB 0 65535 — 1 V Get
358 40259 VAB ANGLE -1800 1800 — 10 ° Get
359 40260 VBC 0 65535 — 1 V Get
360 40261 VBC ANGLE -1800 1800 — 10 ° Get
361 40262 VCA 0 65535 — 1 V Get
362 40263 VCA ANGLE -1800 1800 — 10 ° Get
363 40264 AVERAGE LINE 0 65535 — 1 V Get
364 40265 VAN 0 65535 — 1 V Get
365 40266 VAN ANGLE -1800 1800 — 10 ° Get
366 40267 VBN 0 65535 — 1 V Get
367 40268 VBN ANGLE -1800 1800 — 10 ° Get
368 40269 VCN 0 65535 — 1 V Get
369 40270 VCN ANGLE -1800 1800 — 10 ° Get
370 40271 VG 0 65535 — 1 V Get
371 40272 VG ANGLE -1800 1800 — 10 ° Get
372 40273 AVERAGE PHASE 0 65535 — 1 V Get
373 40274 VOLTAGE IMBAL 0 1000 — 10 % Get
Power Data
374 40275 REAL POWER -32768 32767 — 1 kW Get
375 40276 REACTIVE POWER -32768 32767 — 1 kVAR Get
376 40277 APPARENT POWER -32768 32767 — 1 kVA Get
377 40278 POWER FACTOR -100 100 — 100 — Get
Group
DeviceNet
Param No.
Modbus Register
Parameter Name Min Max Default
Scale
Factor
Units Access
Read (0x03h) Write (0x06h)