72 Rockwell Automation Publication 825-UM004D-EN-P - November 2012
Chapter 6 Configuring Protection & Logic Functions
If the Locked Rotor Ampere rating for the motor is unknown, but the motor
has a Motor Code designation, use the following table as provided by NEMA
(National Electrical Manufacturer Association) to determine the locked rotor
ampere value.
Locked kVA per horsepower range includes the lower figure up to, but not including, the higher figure; e.g., 3.14 is designated by letter
A and 3.15 is designated by letter B.
EXAMPLE
Thermal Element Setting
A 4000V 600 Hp motor is protected using the 825-P Thermal Overload Element. Motor
data sheet includes the following:
Rated Horsepower = 600 Hp
Rated Voltage = 4000V
Rated Full Load Current = 80 A
Rated Locked Rotor Amps = 480 A
Safe Stall Time at 100% Volts:
Cold = 18 seconds
Hot = 15 seconds
Service Factor = 1.2
Phase current transformers with 100:5 A rating and the MCM20 module are selected
for application. 825-P settings for application are calculated as shown below:
Current Transformer Ratio: := 100/5 := 20
Full Load Amps (Ie): := 80 A primary
Service Factor: := 1.2
Locked Rotor Amps: := 480.0/80.0 := 6.0 x Ie
Hot Locked Rotor Time: := 15.0 seconds
Run state time constant: := Auto
NOTE: To prevent nuisance tripping from occurring when a motor operates at the rated service
factor, set Service Factor to 0.01 plus the motor nameplate value.
Table 12 - Motor Codes
Letter Designation kVA/HP Letter Designation kVA/HP
A 0…3.15 L 9.0…10.0
B 3.15…3.55 M 10.0…11.2
C 3.55…4.0 N 11.2…12.5
D 4.0…4.5 P 12.5…14.0
E 4.5…5.0 R 14.0…16.0
F 5.0…5.6 S 16.0…18.0
G 5.6…6.3 T 18.0…20.0
H 6.3…7.1 U 20.0…22.4
J 7.1…8.0 V 22.4 and up
K 8.0…9.0