EasyManua.ls Logo

Allen-Bradley ControlLogix 1756 - Page 136

Allen-Bradley ControlLogix 1756
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1756-RM084F-EN-P - July 2002
A-8 Valid CommMethod and ConfigMethod Values
1756-OA8 Output Data 20000001 00800001
Scheduled Output Data 20000002 00800002
Listen Only - Output Data 28000001 00800003
Rack Optimized 40000000 00800004
1756-OA8D Full Diagnostics - Scheduled Output Data 20000001 00800001 (standard)
00800002 (diagnostic)
Full Diagnostics - Output Data 20000002 00800003 (standard)
00800004 (diagnostic)
Listen Only - Full Diagnostics - Output Data 28000001 00800005
Rack Optimized 40000000 00800006
1756-OA8E CST Timestamped Fuse Data - Scheduled Output Data 20000001 00800001 (standard)
00800002 (fused)
CST Timestamped Fuse Data - Output Data 20000002 00800003 (standard)
00800004 (fused)
Listen Only - CST Timestamped Fuse Data - Output Data 28000001 00800005
Rack Optimized 40000000 00800006
1756-OA16 CST Timestamped Fuse Data - Scheduled Output Data 20000001 00800001
CST Timestamped Fuse Data - Output Data 20000002 00800002
Listen Only - CST Timestamped Fuse Data - Output Data 28000001 00800003
Rack Optimized 40000000 00800004
1756-OA16I Output Data 20000001 00800001
Scheduled Output Data 20000002 00800002
Listen Only - Output Data 28000001 00800003
Rack Optimized 40000000 00800004
1756-OB8 Output Data 20000001 00800001
Scheduled Output Data 20000002 00800002
Listen Only - Output Data 28000001 00800003
Rack Optimized 40000000 00800004
1756-OB8EI CST Timestamped Fuse Data - Scheduled Output Data 20000001 00800001
CST Timestamped Fuse Data - Output Data 20000002 00800002
Listen Only - CST Timestamped Fuse Data - Output Data 28000001 00800003
Rack Optimized 40000000 00800004
1756-OB16D Full Diagnostics - Scheduled Output Data 20000001 00800001 (standard)
00800002 (diagnostic)
Full Diagnostics - Output Data 20000002 00800003 (standard)
00800004 (diagnostic)
Listen Only - Full Diagnostics - Output Data 28000001 00800005
Rack Optimized 40000000 00800006
1756-OB16E CST Timestamped Fuse Data - Scheduled Output Data 20000001 00800001
CST Timestamped Fuse Data - Output Data 20000002 00800002
Listen Only - CST Timestamped Fuse Data - Output Data 28000001 00800003
Rack Optimized 40000000 00800004
I/O Module: Configuration: CommMethod Value: ConfigMethod Value:

Table of Contents