Publication 1756-RM084F-EN-P - July 2002
Creating a Complete Import/Export File 3-7
Specifying a MODULE connection list
You can specify these attributes for a connection list:
CONNECTION <
connection_name
> [
Attributes
]
[InputData := <
value_list
>;]
[InputForceData := <
value_list
>;]
[OutputData := <
value_list
>;]
[OutputForceData := <
value_list
>;]
END_CONNECTION
Where:
For details on the data in the connection list, see the user manual for
the I/O module. The connection list data depends on the I/O module
and the configuration for that module.
Forces appear as arrays of bytes under the InputForceData and
OutputForceData attributes of the connection list. Do not modify
forces in the import/export file. Use the programming software to
enter and enable forces.
ChABaud
For a 1756-DHRIO module, specify the baud rate for channel A. Enter 57.6, 115.2, or 230.4.
Specify:
ChABaud :=
baud
ChBBaud
For a 1756-DHRIO module, specify the baud rate for channel B. Enter 57.6, 115.2, or 230.4.
Specify:
ChBBaud :=
baud
RSNetWorxFileName
Specify the file name of an associated RSNetWorx project file.
Specify:
RSNetWorxFileName :=
filename
Attribute: Description:
Item: Identifies:
connection_name
the connection
InputData
input channel data
InputForceData
forcing information for the input channel
OutputData
output channel data
OutputForceData
forcing information for the output channel
Attributes
attributes of the connection
can also contain a description of the module
separate each attribute with a comma (,)
Spare Allen-Bradley Parts