72 Rockwell Automation Publication 2080-UM004D-EN-E - March 2018
Appendix A Specifications
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40...85 °C (-40…185 °F)
Temperature, surrounding air,
max
65 °C (149 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5%...95% non-condensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
2g @ 10...500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
35 g (PANEL mount)
Emissions CISPR 11 (IEC 61000-6-4):
Class A
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1kH sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1kHz sine-wave 80% AM from 2000...2700 MHz
Altitude, operating 2000 m
Certifications – 2080-MEMBAK-RTC, 2080-MEMBAK-RTC2, 2080-TRIMPOT6
Certification (when
product is marked)
(1)
(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification/ for
Declarations of Conformity, Certificates, and other certification details.
Value
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E334470.
CE European Union 2014/30/EU EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
RCM Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation
Specifications – 2080-TRIMPOT6
Attribute Value