Rockwell Automation Publication 2080-UM004D-EN-E - March 2018 71
Specifications Appendix A
Specialty Plug-in Modules
Specifications – 2080-MEMBAK-RTC, 2080-MEMBAK-RTC2
Attribute Value
Resolution READ_RTC() 1 s
Accuracy ± 5 sec/month @ 25 °C
± 9 sec/month@ -20…65 °C
Power off Battery — 3.5 years from date of manufacture @ 25…65 °C, 2.5
years from date of manufacture @ 0 °C
Temperature, operating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-20...65 °C (-4…149 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40...85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
2g @ 10...500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
35 g (PANEL mount)
Emissions CISPR 11 (IEC 61000-6-4):
Class A
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1kH sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1kHz sine-wave 80% AM from 2000...2700 MHz
Altitude, operating 2000 m
IMPORTANT
Battery life does not include controller ON time. For example, if the
Controller is ON for 16 hours every day for 365 days, if the module starts
being used after 1 year of manufacturing, battery life is 8.5 years (1 year
initial time + 2.5 years of Off time out of 7.5 years).
Specifications – 2080-TRIMPOT6
Attribute Value
Data range 0…255
Number of trimpot 6
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4…149 °F)

Table of Contents