3 Contactor Full Feature Bypass with Disconnect Package (Style B/N) 2-35
Rockwell Automation Publication 22C-IN002E-EN-P - November 2010
Figure 2.23 3.0…50 Hp, 208V & 3.0…150 Hp, 460V AC Drives -
NEMA/UL Type 12, 4, 3R
97D01549
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
01
DATEREV. BY ECN/CR. NO.
A 11/14/06 REH
APPROVAL
DESIGN REVIEW
FOR MANUFACTURING
AS SHIPPED
AS COMMISSIONED
BYDATE
SH.NEXT
NO.SH.
-
DWG.ENG.
TITLE
CHK. BY
NO.DATE DATE
DR. BY
DATE
THIS DRAWING IS THE PROPERTY OF ROCKWELL AUTOMATION, INC.
OR ITS SUBSIDIARIES AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY
PURPOSE EXCEPT AS AUTHORIZED IN WRITING BY ROCKWELL AUTOMATION, INC.
11
INTER-CONNECT DRAWING - PF400, STYLE B
3-50HP @ 208VAC, 3-150HP @ 460VAC
NEMA 3R, 4, 12
97D01549
JRF/ACI
11/23/06
JCL/ACI
02/17/06
JFH/ACI
11/23/06
CONNECTIONS SUPPLIED BY CUSTOMER
WILL REQUIRE MANUAL RESET.
OPENING OF THE FREEZE/FIRE INTERLOCK
1
3231 33 34 35 36 37 38 39
BC
BYPASS
RUN
PURGE
40
AUTO START
BYPASS
STATUS
INTERLOCKS
FREEZE/FIRE
R/L1
T/L3
S/L2
GP2P1
U/T1
POWERFLEX 400
W/T3
V/T2
SPEED REF. INPUT
4-20MA, 250 OHM
INPUT IMPEDANCE
+
2
10V 20MA
RUN/FWD
FUNCTION LOSS
SOFTWARE ENABLE
DIGITAL INPUT 1 (PURGE)
DIGITAL COMMON
DIGITAL INPUT 2 (LOCAL)
DIGITAL INPUT 3 (ANALOG 1 IN)
DIGITAL COMMON
DIGITAL INPUT 4 (COMM PORT)
1324 756 89
10V 20MA
CONTROL BOARD
AO2
10V 20MA
AO1 AI1
ANALOG COM. #1
ANALOG OUTPUT #2 (OUTPUT CURRENT 0-10V)
ANALOG OUTPUT #1 (FREQUENCY 0-10V)
ANALOG INPUT #1
+ 10VDC
+ 24VDC
ANALOG INPUT #2
#1 RELAY N.O. (READY/FAULT)
ANALOG COM #2
OPTO OUTPUT (AT FREQUENCY)
#1 RELAY COMMON
#1 RELAY N.C.
#2 RELAY N.O. (MOTOR RUNNING)
#2 RELAY COMMON
#2 RELAY N.C.
RJ-45 SHIELD
OPTO COMMON
151110 12 13 14 16 17 1918 20 R3R1 R2 R4 R5 R6
SRC
10V 20MA
AI2
SNK
DM1
2
WHEN IN "AUTO MODE" SPEED REFERENCE WILL
COME FROM 4-20ma SOURCE WIRED TO ANALOG
INPUT #2. IF 0-10V SOURCE IS TO BE USED,
CHANGE PARAMETER T73 TO "2" VOLTAGE MODE AND
SET DIP SWITCH "AI2" TO 10V.
INCOMING
3
f POWER
MAIN
DISCONNECT
SWITCH
GROUND
DS1
T2T1 T3
MG
CUSTOMER CONNECTION
T1 T2 T3
MOTOR
TB1
L3L2L1GND
TB2