5-2 Electrical Installation
Rockwell Automation Publication 22C-IN002E-EN-P - November 2010
Control and Signal Wiring
The terminal block on the Main Control board provides terminals for 24V
DC power for the eight remote control inputs and outputs. The terminal
block in the options cabinet provides terminals for 115V AC power for the
remote control inputs and outputs. The options cabinet terminal block is
factory-wired to the terminal block on the Main Control board.
Installing Input Power
Wiring
To connect AC input power to the drive:
Step 1. Wire the AC input power leads by routing them according to drive
type. Power wiring sizes are listed in Table 5.A
.
Step 2. Connect the three-phase AC input power leads (three-wire V AC)
to the appropriate terminals. Connect the AC input power leads to
terminals R/L1, S/L2, T/L3 on the power terminal block.
Step 3. Tighten the AC input power terminals to the proper torque
according to drive type as shown in Table 5.A
.
Output Power
T1(U), T2(V), T3(W)
A 310 320 16 AWG 8 AWG 26
15…30 25…40 8 AWG 2 AWG 45
50…60 12 AWG 2 AWG 49.5
40…50 75…150 1/0 AWG 4/0 AWG 173
200…250
(1) (1)
260
300…350
(1) (1)
354
B 3…7.5 3…7.5 22 AWG 8 AWG 13
10…20 10…30 14 AWG 4 AWG 19
25…30 40…75 12 AWG 1/0 AWG 40
100…150 6 AWG 350 MCM 275
40…50 200…300 (2) 4 AWG 350 MCM 500
350 (2) 250 MCM 750 MCM 375
C 3…7.5 22 AWG 8 AWG 13
10…30 14 AWG 4 AWG 19
40…75 12 AWG 1/0 AWG 40
100 (2) 1/0 AWG 350 MCM 275
(1)
Threaded studs provided for wire lugs.
Name Package
Hp Wire Size Range
Torque208V AC 480V AC Minimum Maximum
!
ATTENTION: Protect the contents of the options cabinet
from metal chips and other debris while drilling the conduit
openings. Failure to observe this precaution could result in
damage to, or destruction of, the equipment.
!
ATTENTION: Do not route signal and control wiring with
power wiring in the same conduit. This can cause interference
with drive operation. Failure to observe this precaution could
result in damage to, or destruction of, the equipment.

Table of Contents

Other manuals for Allen-Bradley PowerFlex 400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 400 and is the answer not in the manual?

Allen-Bradley PowerFlex 400 Specifications

General IconGeneral
Input Voltage200-240VAC, 380-480VAC, 500-600VAC
Output Voltage0-Input Voltage
Output Frequency0-400 Hz
CommunicationEtherNet/IP
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short Circuit
Operating Temperature-10°C to 50°C (14°F to 122°F)
Storage Temperature-40°C to 70°C (-40°F to 158°F)
Humidity5-95% non-condensing
Enclosure RatingIP20
Horsepower0.5-20 HP
Control MethodV/Hz, Sensorless Vector Control