5-2 Electrical Installation
Rockwell Automation Publication 22C-IN002E-EN-P - November 2010
Control and Signal Wiring
The terminal block on the Main Control board provides terminals for 24V
DC power for the eight remote control inputs and outputs. The terminal
block in the options cabinet provides terminals for 115V AC power for the
remote control inputs and outputs. The options cabinet terminal block is
factory-wired to the terminal block on the Main Control board.
Installing Input Power
Wiring
To connect AC input power to the drive:
❏ Step 1. Wire the AC input power leads by routing them according to drive
type. Power wiring sizes are listed in Table 5.A
.
❏ Step 2. Connect the three-phase AC input power leads (three-wire V AC)
to the appropriate terminals. Connect the AC input power leads to
terminals R/L1, S/L2, T/L3 on the power terminal block.
❏ Step 3. Tighten the AC input power terminals to the proper torque
according to drive type as shown in Table 5.A
.
Output Power
T1(U), T2(V), T3(W)
A 3…10 3…20 16 AWG 8 AWG 26
15…30 25…40 8 AWG 2 AWG 45
– 50…60 12 AWG 2 AWG 49.5
40…50 75…150 1/0 AWG 4/0 AWG 173
– 200…250
(1) (1)
260
– 300…350
(1) (1)
354
B 3…7.5 3…7.5 22 AWG 8 AWG 13
10…20 10…30 14 AWG 4 AWG 19
25…30 40…75 12 AWG 1/0 AWG 40
– 100…150 6 AWG 350 MCM 275
40…50 200…300 (2) 4 AWG 350 MCM 500
– 350 (2) 250 MCM 750 MCM 375
C – 3…7.5 22 AWG 8 AWG 13
– 10…30 14 AWG 4 AWG 19
– 40…75 12 AWG 1/0 AWG 40
– 100 (2) 1/0 AWG 350 MCM 275
(1)
Threaded studs provided for wire lugs.
Name Package
Hp Wire Size Range
Torque208V AC 480V AC Minimum Maximum
ATTENTION: Protect the contents of the options cabinet
from metal chips and other debris while drilling the conduit
openings. Failure to observe this precaution could result in
damage to, or destruction of, the equipment.
ATTENTION: Do not route signal and control wiring with
power wiring in the same conduit. This can cause interference
with drive operation. Failure to observe this precaution could
result in damage to, or destruction of, the equipment.