3 Contactor Basic Bypass with Disconnect Package (Style C) 3-7
Rockwell Automation Publication 22C-IN002E-EN-P - November 2010
Operating Modes
Drive Mode
For this mode to be active, the door-mounted selector switch needs to be in
the DRIVE position. The DIC and DOC are energized and the BC is
de-energized.
When the drive is in HAND configuration, the start command comes from
the integral keypad Start/Hand key. The speed reference come from the
Digital Increment and Decrement keys.
When the drive is in AUTO configuration, the start command is set for
two-wire control. The drive runs when there is a closed contact between
terminals 19-20 located inside the Option Cabinet and stops when the
contact is open. Parameter P038 [Speed Reference] determines the source of
the speed reference. The drive package ships with the speed reference
configured for Analog In1 which would be wired to signal terminals 13-14
located on the drive. Refer to the PowerFlex 400 User manual for
information on other control schemes.
Test Mode
For this mode to be active, the door-mounted selector switch needs to be in
the “Test” position. The DIC is energized and the DOC and BC are
de-energized.
Off Mode
For this mode to be active, the door-mounted selector switch needs to be in
the “Off” position. The DIC, DOC and BC are all de-energized. The
PowerFlex drive will not be powered and the motor will not run.
Bypass Mode
In the Bypass Mode the BC is energized and the DIC and DOC are
de-energized. The motor is powered by the AC line. The motor will
immediately be powered when the selector switch is in the “Bypass”
position unless the “Drive/Bypass Enable” relay, CR, is used and is not
picked up.