2.4 WIRE SIZING
Care must be taken to properly size all conductors for the input and output of the power
supply. Table 2-5 below gives minimum recommended wire size for the input. This
table is derived from the National Electrical Code and is for reference only. Local laws
and conditions may have different requirements. The table is for copper wire only.
Table 2-6
Minimum Wire SizeTable
SIZE
60 °C 75 °C 85 °C 90 °C
TYPES TYPES TYPES TYPES
AWG
MCM
RUW, T, TW,
UF
FEPW, RH,
RHW, RUH,
THW, THWN,
XHHW, USE,
ZW
V, MI TA, TBS, SA,
AVB, SIS, FEP,
FEPB, RHH,
THHN, XHHW
14 20 20 25 25
12 25 25 30 30
10 30 35 40 40
840505555
655657075
470859595
3 85 100 110 110
2 95 115 125 130
1 110 130 145 150
0 125 150 165 170
00 145 175 190 195
000 165 200 215 225
0000 195 230 250 260
TEMPERATURE RATING OF COPPER CONDUCTOR
CURRENT RATING
For higher ratings wires can be paralleled or refer to the National Electrical Code.
2.5 OUTLINE DRAWINGS
The following pages (figures 2-1 through 2-6) show the outlines and overall dimensions
for the DHP product lines.