Storage Temperature
Recharge Frequency
Charging Duration
-13°F to 104°F (-25°C to +40°C)
Every 3 Months
1-2 Hours
104°F to 113°F (40°C to +45°C)
Every 2 Months
1-2 Hours
2.5 Environmental Conditions
The UPS must be installed on a level and even surface. Install in an area
protected from extremes of temperature, water, humidity and the pres-
ence of conductive powder or dust. Do not stack units and do not place
any objects on top of a unit.
The functional temperature range of the UPS is 32°F to 104°F (0°C to
+40°C).
The ideal ambient temperature range is 60°F to 77°F (15°C to 25°C).
Expected battery runtimes and battery life is based on operational tem-
peratures between 68°F and 77°F (20°C and 25°C). Operation of the
equipment above 77°F (25°C) reduces the service life of the batteries
dramatically.
2.6 Floor Loading
Taking into consideration the weight of the UPS, extended battery cab-
inets, and any other equipment that may be mounted in an associated
rack. Confirm that the floor
chosen
location is
capable
of
supporting
the
weight of the combined units.
2.7 Ventilation
It is necessary to leave a minimum space of at least two inches (50 mm)
in front and rear of the UPS to allow a flow of
air
.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ametek Surgex UPS-17202-53R and is the answer not in the manual?

Ametek Surgex UPS-17202-53R Specifications

General IconGeneral
BrandAmetek
ModelSurgex UPS-17202-53R
CategoryUPS
LanguageEnglish

Related product manuals