4.2.4 Bypass Mode Enable /Disable when the UPS is off (Item 06)
ENA: Bypass mode is enabled when the UPS is turned off.
When the UPS is first
plugged
in, it
will
enter
bypass
mode, or if the UPS is in on-line mode and then turned off,
it will enter bypass mode.
DIS: Bypass mode is disabled when the UPS is turned
of
f.
When the UPS is first
plugged
in, it
will
enter
standby
mode with no output, or if the UPS is in on-line
mode and then turned off , it will enter standby mode with
no output.
4.2.5 Programmable Outlets Enable /Disable (Item 07)
ENA: Programmable outlets are enabled. When the UPS
goes to Battery mode the programmable outlets will supply
power to the connected load for a duration equal to the
timer setting in section 4.0 or until the battery becomes
depleted,
whichever
occurs first.
DIS: Programmable outlets are disabled. When the UPS
goes to battery mode the programmable outlets will supply
power to the connected load until the battery becomes
depleted.
4.2.6 Programmable Outlets Setting (Item 08)
0-999: Backup time in minutes that programmable output
receptacles will operate in battery mode.