EasyManua.ls Logo

Armstrong 4280 - Digital Output; Relay Output; Supply Voltage; Supply Fusing

Armstrong 4280
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
installation &
operating instructions
Design Envelope 4200h & 4280
End Suction Horizontal Pumping Units
17
c setting the differential pressure (dp) sensor through lcd
Set the current\ voltage DP sensor setting:
• Set Sensor Signal Intervals
• Set Sensor Pressure range
• Set desire zone pressure
• Click Confirm
2.3.6 digital output
If either of the digital outputs are to be used for voltage dif-
ferential, a 500 ohm resistor (supplied by others) must be con-
nected between the respective digital output and the 24VEXT
terminal. Refer to fig 2.3.6
fig 2.3.6
2.3.7 relay output
J5 & J8 for Relay output
j8
n.o. 2 Relay n.o.
n.c. 2 Relay n.c.
com2 Relay 2A 250Vac
j5
n.o. 1 Relay n.o.
n.c. 1 Relay n.c.
com 1
Relay 2A 250Vac
2.3.8 supply voltage
The supply voltage details can be found on the 4200h &
4280 nameplate. Please ensure that the unit is suitable for the
electrical supply on which it is to be used. The mains supply for
Design Envelope pumps is as follows:
1 × 200-230v ± 10% ,
3 × 200-230v ± 10% ,
3 × 380-480v ± 10%,
3 × 575-600v ± 10%
Frequency - 50/60Hz
2.3.9 supply fusing
Branch circuit protection
in order to protect the installation against electrical and fire
hazard, all branch circuits in an installation, switch gear, ma-
chines etc., must be short-circuit and over-current protected
according to the national/international regulations. Please refer
to section 8.0 (Fuse and wire recommendation).
Short circuit protection
The inverter must be protected against short-circuit to avoid
electrical or fire hazard. The frequency converter provides full
short circuit protection in case of a short-circuit on the motor
output.
V
V
500 Ohm
500 Ohm

Table of Contents

Related product manuals