6.2 AUTO-RESTART FEATURE, cont.
6.2.1 Operation
Auto-Restart is enabled in the Auto-Restart Control panel accessed by simultaneously pressing two
buttons. Anytime the Systems Status is “FAILURE,” the converter will disable the Auto-Restart
feature. Every time the Shore Power OFF button is pressed the converter will disable the Auto-
Restart feature. The converter must be ON and ONLINE before Auto-Restart may be enabled.
Pressing the “SYSTEM STATUS” button (7) will display the “SUMMARY DISPLAY” which will
indicate the Auto-Restart status.
CONVERTER ACTION FRONT PANEL OPERATION
Enter Auto-Restart Control panel SHORE POWER(5) & CONVERTER POWER(6)
Follow the on-screen instructions to enable or disable the feature.
6.3 TURN-OFF PROCEDURE
Transfer power from the AC08 or AC12 to the generator.
Press the CONVERTER POWER OFF (4) button. The indicator LED should change to red. If the
STATUS display is active, it should indicate CONVERTER:OFFLINE. Power has now been
removed from the output, but the system remains active. This is the systems “standby” state.
Next press the SHORE POWER OFF (3) button. This will initiate the inverter shutdown. The
system will complete the shutdown process within 10 seconds.
Turn the disconnect switch (10) to the OFF position.
Open the input (shore power) circuit breaker to the AC12.
The AC08 or AC12 is now shut down.