9.3 Flow Chart Relay Setting
9.3.1 To Set Relay Setting
Password = 000
Use Inr/Dec
New Password = 000
Use Inr/Dec
Unit ID = 001
IP> = 050
Range 5 – 250%
5
Relay Setting
-
3
IP> TMS = x0.010
Range x0.010 to x1.50
IP>> = 0100
Range 50 – 3000%
IE> = 025
Range 5% – 250%
IE> TMS = x0.010
Range x0.010 to x1.50
IE>> = 0100
Range 50 – 3000%
IP> Curve = C1
Range C1 – C6
IE> Curve = C1
Range C1 – C6
IP> C6 Time = 01.0
Range 0-99.9S
IE> C6 Time = 01.0
Range 0-99.9S
IP>> Delay = 00.10
Range 0 – 10.00S
IE>> Delay = 00.10
Range 0 – 10.00S
5 6 5 6 5 6 5 6
5 6
5 6
5 6
5 65 6
5 6
5 6
5 6 5 6
5 6
5 6
BF Delay = 200
Range 000 – 800ms
5 6
CT Sec. = 001
1 = 1A, 2 = 5A
OK
5 6
CT Primary = 0100
Range 10 – 5000
5
5 6
5 6
Test Block = 02
01= Yes, 02 = No
Trip Ckt = 02
01= Yes, 02 = No
5 6
5 6
Ann Type = 001
Range 1 – 4
Ann Cont. = 001
SR = 1 HR = 2
5 6
5 6
Trip Cont. = 001
SR = 1 HR = 2
BF Cont. = 001
SR = 1 HR = 2
5 6
Com Port = USB
USB/RS485
5 6
5 6
Set Parity = None
None/Even/Odd
Baud Rate = 008
Range 1 – 8
Save setting?
Mode (3) For Save
Note: The display pages shown in dashed lines are only for ADR241A Relay.