ADR141A /
ADR241A
Ref ID : ADR241A/IM/UG
Rev No. : 02
8.3.5 Cold Load Settings
8.3.5.1 To Set – Cold Load Settings
COLD LOAD
Password protected window for “Cold Load” setting i.e. CL
Enable, CL Timer, CL IP>, CL IP>TMS, CL IP>>. CL IE>, CL
IE>TMS, CL IE>>, CL IP> Curve, CL IE> Curve, CL IP> C6
Time, CL IE> C6 Time, CL IP>> Delay and CL IE>> Delay
Press the Plus / Up arrow key (+ /) to move to the next option.
Password
0001
Editable setting
Enter the set password, by using the up arrow key (+ /) or
the down arrow key (- /).
Press the Left arrow key () to move to the next option.
CL Enable = 002
01: YES, 02: NO
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the desired Cold Load Enable function can
be set i.e. Yes / No.
Press the Left arrow key () to move to the next option.
CL Timer = 10.0
Range 0.1 – 10.0S
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the desired CL Timer can be set.
The setting range is from 0.10 to 10.0s in steps of 0.1s.
Press the Left arrow key () to move to the next option.
CL IP> = 050
Range 5 – 250%
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the desired CL IP> can be set.
The setting range is from 5% to 250% in steps of 1%.
Press the Left arrow key () to move to the next option.
CL IP> TMS = x0.010
Range X0.01 – 1.50
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the desired CL IP> TMS can be set.