9.4 Flow Chart Cold Load
9.4.1 To Set Cold Load
Password
0001
CL Enable = 002
01: YES, 02: NO
CL IP> = 050
Range 5 – 250%
CL IP> TMS = x0.010
Range X0.01 – 1.50
5
Cold Load
CL IP>> = 0100%
Range 50 – 3000%
CL IE> = 025
Range 5 – 250%
CL IE>Curve =C1
Range C1 – C6
CL IP>C6Time = 01.0
Range 0 – 99.9S
CL IE>C6Time = 01.0
Range 0 – 99.9S
5 6
5 6 5 6 5 6 5 6 5 6
5 65 65 6
CL IE>> = 0100%
Range 50 – 3000%
5 6
CL IP>>Delay = 00.10
Range 0 – 10.00S
5 6
CL IE> TMS = x0.010
Range X0.01 – 1.50
5 6
CL IE>>Delay = 00.10
Range 0 – 10.00S
CL IP>Curve =C1
Range C1 – C6
5 6
5
3
OK
Save setting?
Mode (3) For Save
5 6
CL Timer = 10.0
Range 0.1 – 10.0S