EasyManua.ls Logo

Ashida ADR141C - Page 33

Ashida ADR141C
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 33/86
IP>> 001
Multiply by 50
By using the up arrow key ( +
/
) or the down arrow key
( - /) the IP>> can be set in range of multiply by 50.
Press the left arrow key () the relay will display as follows.
3Io> Enable = YES
01 = YES , 02 = N0
By using the up arrow key ( +
/
) or the down arrow key
( - /) the desired 3Io> Enable can be selected . i.e. YES
or NO. If set YES then 3Io> setting is enabled and if set NO
then it will be disabled
Press the left arrow key () the relay will display as follows.
3Io>> = 001
Multiply by 50
By using the up arrow key ( +
/
) or the down arrow key
( - /) the desired 3Io>> can be set. The setting range is
Multiply of 50 in steps of 1.
Press the left arrow key () the relay will display as follows.
3Io> TMS = X1.00
Range X0.01 – 1.00
By using the up arrow key ( +
/
) or the down arrow key
( - /) the desired 3Io> TMS can be set. The setting range
is from X0.01 – 1.00 in steps of 0.01.
Press the left arrow key () the relay will display as follows.
Ip Curve = 006
Range C1 C6
By using the up arrow key ( +
/
) or the down arrow key
( - /) the desired Ip Curve can be selected. Six different
types of curves are provided from C1 to C6. When the
given value is 001, curve 1 is selected and when the given
value 002, curve 2 is selected.
In similar manner any desired curve can be selected as 001
to 006 correspond respectively with C1 to C6.
Press the left arrow key () the relay will display as follows.
3Io> = 200
Range 10
250%
By using the up arrow key ( +
/
) or the down arrow key
( - /) the desired 3Io> can be set. The setting range is
from 10% to 250% in steps of 1%.
Press the left arrow key () the relay will display as follows.
3Io>> Enable = YES
01 = YES , 02 = N0
By using the up arrow key ( +
/
) or the down arrow key
( - /) the desired 3Io>> Enable can be selected . i.e. YES
or NO. If set YES then 3Io>> setting is enabled and if set
NO then it will be disabled
Press the left arrow key () the relay will display as follows.

Table of Contents