NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 61/86
9.4 Flow Chart – To Set & To View COLD LOAD Settings
Ip>> Delay = 0.00
Range 0 – 2.00S
Ip> Enable = Yes
01 : YES, 02 : NO
CL Enable = Yes
01 : YES, 02 : NO
Ip>> = 020
Multiply by 50
3Io>> Delay = 0.00
Range 0 – 2.00S
IpTMS= X1.00
Range X0.01 – 1.00
Cold Load Settings
CL Enable = NO
CL Timer = 0.50
Ip> 250% t=x1.00
Ip>> 1000%
3Io>> Enable = Yes
01 : YES, 02 : NO
3Io> = 250
Range 10 – 250%
Ip Curve = 001
Range C1 – C6
Ip> Enable = No
Ip>>Enable = No
CL Timer = 01.00
Range 0.1 – 10.0S
Password = 0000
Use Inr/Dec
Ip>> Enable = Yes
01 : YES, 02 : NO
Ip> = 250
Range 10 – 250%
3Io TMS = X1.00
Range X0.01 – 1.00
3Io> Enable = Yes
01 : YES, 02 : NO
3Io Curve = 001
Range C1 – C6
3Io>> = 020
Multiply by 50
3Io> Enable = No
3Io>> Enable = No
Ip> Normal Inv. 1
3Io> Normal Inv. 1
3Io> 250% t=x1.00
3Io>> 1000%
Ip>> Delay = 0.00
3Io>> Delay = 0.00
Ip> C6 Del = 00.5
Range 0.1 – 99.9S
3IO> C6 Del = 00.5
Range 0.1 – 99.9S
Save setting?
Mode for Save
Ip> C6 Del = 00.5
3Io> C6 Del = 01.0
OK