NUMERICAL OC/EF PROTECTION RELAY ADR141C/241C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page 37/86
IP> TMS = X1.00
Range X0.01 – 1.0
By using the up arrow key ( + / ) or the down arrow key
( - /) the IP> TMS can be set in range of X0.01
– 1.0 in
step of 0.01
Press the left arrow key () the relay will display as follows.
Ip>> Enable = YES
01 = YES , 02 = N0
By using the up arrow key ( +
) or the down arrow key
( - /) the desired IP>> Enable can be selected i. i.e. YES
or NO. If set YES then BF setting is enabled and if set NO
then it will be disabled
Press the left arrow key () the relay will display as follows.
3Io> TMS = X1.00
Range X0.01 – 1.00
By using the up arrow key ( +
) or the down arrow key
( - /) the desired 3Io> TMS can be set. The setting range
is from X0.01 – 1.00 in steps of 0.01.
Press the left arrow key () the relay will display as follows.
Ip>> = 001
Multiply by 50
By using the up arrow key ( +
) or the down arrow key
( - /) the desired Ip>> can be set. The setting range is
multiply of 50 in steps of 1.
Press the left arrow key () the relay will display as follows.
3Io>> Enable = YES
01 = YES , 02 = N0
By using the up arrow key ( +
) or the down arrow key
( - /) the desired 3Io>> Enable can be selected .e. YES or
NO. If set YES then 3Io>> setting is enabled and if set NO
then it will be disabled
Press the left arrow key () the relay will display as follows.
3Io> Enable = YES
01 = YES , 02 = N0
By using the up arrow key ( +
) or the down arrow key
( - /) the desired 3Io> Enable can be selected . i.e. YES
or NO. If set YES then 3Io> setting is enabled and if set NO
then it will be disabled
Press the left arrow key () the relay will display as follows.
3Io> = 250
Range 10
– 250%
By using the up arrow key ( +
) or the down arrow key
( - /) the 3Io> can be set in Range 10
– 250% in steps of
001%
Press the left arrow key () the relay will display as follows.