8.3.2 Hot Water (HW)
"Comfort T° charge": DHW program + o-peak hours / O-peak hours / Permanent.
Electrical back-up power: 0 to 20 KW.
Conguration
Comfort T° charge
Electrical back-up power
1KW
DHW Circuit
DHW program + o-peak hours
See "Time programming", page 54.
" DHW period factory setting: 00:00 - 05:00, 14:30 - 17:00.
"Comfort T°": ECO Temp Setpoint … 65°C.
"ECO T°": 8°C... Comfort Temp setpoint.
" DHW temperature factory settings: Comfort 55°C, ECO 40°C.
Setpoint settings
Comfort T°
55°C
ECO T° 40°C
DHW Circuit
"Anti-legionella": Stop, ON.
"Day of treatment": Monday / Tuesday / Wednesday / Thursday / Friday / Saturday /
Sunday.
"Hour of treatment": 00:00.
"Setpoint T°": 55°C... 95°C.
Anti-legionella management
Day of treatment Sunday
Anti-legionella
Stop
Hour of treatment ---
Setpoint T° 60°C
DHW Circuit
Some settings (or menus) might not be displayed. They are dependent on the installation's conguration (and installed options).
Hydraulic conguration Hot water
General Conguration
Time programming
Setting setpoint T°
Anti-legionella management
Installation and Operating Manual "1821- EN" - 55 -
Alféa Extensa Duo A.I. Heat Pump